14 Parameter reference
14.2 Parameter list | C00601
802
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00601
C00604
C00606
Parameter | Name:
C00601 | Resp. to encoder comm. error
Data type: UNSIGNED_32
Index: 23974
d
= 5DA6
h
Response to activation of encoder monitoring
• For the use of the encoder as motor encoder: If an error occurs, the safe operation of the motor is no longer
ensured, therefore for safety reasons the "Fault" response should always be set!
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
13 Quick Stop open loop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00604 | Resp. to device overload > C00123
Data type: UNSIGNED_32
Index: 23971
d
= 5DA3
h
Response if adjustable "I x t" warning threshold (C00123) is reached.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload > C00127
Data type: UNSIGNED_32
Index: 23969
d
= 5DA1
h
I2xt motor monitoring
Response if adjustable "I
2
x t" warning threshold (C00127) is reached.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1