Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 387
11 Basic drive functions
11.2 Stop
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.2.3 Behaviour of the function (example)
In the following example the enable of manual jog is deactivated during an active manual jog. Then
the drive is braked to standstill within the deceleration time set for stop.
[11-9] Example: Stop with reaching standstill
If the basic function "Manual Jog" is reactivated within the deceleration time , this basic function
takes over the control of the drive from the current speed and the function state "Drive is stopped"
is abandoned immediately:
[11-10] Example: Stop without reaching standstill
C02610: Deceleration time for stop function
C02622
: Manual jog: Acceleration
C02623
: Manual jog: Deceleration
n
t
TRUE
FALSE
MAN_bEnable
t
ManualJog Stopping Standstill ManualJog
TRUE
FALSE
STP_bStopActive
t
TRUE
FALSE
MAN_bJogPositive
t
State
C02610: Deceleration time for stop function
C02622
: Manual jog: Acceleration
C02623
: Manual jog: Deceleration
n
t
TRUE
FALSE
MAN_bEnable
t
ManualJog
Stopping
ManualJog
TRUE
FALSE
STP_bStopActive
t
TRUE
FALSE
MAN_bJogPositive
t
State