Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 747
14 Parameter reference
14.2 Parameter list | C00137
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00137
C00138
C00142
Parameter | Name:
C00137 | Brake transistor utilisation
Data type: INTEGER_32
Index: 24438
d
= 5F76
h
From software version V1.5
Braking operation
Display range (min. value | unit | max. value)
0 % 250
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00138 | Brake resistor utilisation
Data type: INTEGER_32
Index: 24437
d
= 5F75
h
From software version V1.5
Braking operation
Display range (min. value | unit | max. value)
0 % 250
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00142 | Autom. restart after mains ON
Data type: UNSIGNED_32
Index: 24433
d
= 5F71
h
Starting performance of the controller after mains connection and reset of "Trouble", "Fault" or "Safe torque off
active".
Danger!
• If automatic restart is enabled (C00142
= "1: Enabled"), the drive can restart automatically from the "Trouble"
and "Safe torque off" device states when the trouble or request for "Safe torque off active" has been eliminated!
• The controller enable generated by the application via a connection of the terminal 28 (RFR) with one of the
digital outputs DIGOUT_bOut(x) is not permissible if the following functions are active:
"Auto-start after mains ON" (C00142
= "1") and "Program auto-start after mains switching" (C02104 ="1")
If this is not observed, the controller can start automatically after mains connection!
Automatic restart after mains connection
Activate application
Selection list (Lenze setting printed in bold)
0 Inhibited
1Enabled
Read access Write access CINH PLC STOP No transfer Scaling factor: 1