Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 121
5 Motor interface
5.2 Select motor control
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2 Select motor control
In C00006 the motor control is selected; the default is the servo control for synchronous motors.
Function extension from software version V3.0:
From software version V3.0, alternatively to the servo control also the V/f control and the sensorless
vector control are provided as control types in C00006
:
• The V/f control is the classic operating mode for standard applications.
• Compared to the V/f control, improved drive characteristics can be achieved with sensorless
vector control by:
• a higher torque across the entire speed range
• a higher speed accuracy and a higher concentricity factor
• Higher efficiency
[5-1] Comparison of V/f control and sensorless vector control
Open/closed loop control Detailed information
1 SC: Servo control for synchronous motor Servo control (SC)
( 142)
2 SC: Servo control for asynchronous motor
4 SLVC: Sensorless vector control Sensorless vector control (SLVC) ( 163)
6 VFCplus: V/f control open loop V/f control (VFCplus) ( 181)
7 VFCplus: V/f control closed loop V/f control (VFCplus) ( 197)
V/f control
Sensorless vector control
Note!
Sensorless vector control (SLVC) is only approved for powers up to 55 kW and horizontal
applications (no
hoists or lifting equipment)!