13 Diagnostics & fault analysis
13.7 Error messages of the operating system
650
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Motor: Calculated flux factor unrealistic [0x007b000d]
DC bus overvoltage [0x007b000e]
DC bus undervoltage [0x007b000f]
Overcurrent detected [0x007b0010]
Module ID (decimal) Error ID (decimal)
123: Motor control 13
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Faulty motor parameterisation. Check motor parameters.
Module ID (decimal) Error ID (decimal)
123: Motor control 14
Response (Lenze setting printed in bold) Setting: C00600 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Due to a too high braking energy, the DC-bus voltage
exceeds the overvoltage threshold which results from
the mains voltage setting in C00173
.
• Use brake resistor or regenerative module.
•Check setting in C00173
.
Module ID (decimal) Error ID (decimal)
123: Motor control 15
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
DC bus voltage is lower than the undervoltage threshold
resulting from the mains setting under C00173
.
• Check mains voltage.
•Check setting in C00173
.
Module ID (decimal) Error ID (decimal)
123: Motor control 16
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
• Short circuit/earth fault in motor cable.
• Excessive capacitive charging current in the motor
cable.
• Check motor cable.
• Use motor cable that is shorter or has a lower
capacitance.