8 I/O terminals
8.2 Analog inputs
274
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.2 Analog inputs
The controller has two analog inputs that can be used to detect differential voltage signals in the
range of ±10 V, e.g. analog speed setpoint selections or the voltage signals of an external sensor
(temperature, pressure, etc.).
Optionally, analog input 1 can also be used to detect current setpoints.
8.2.1 Terminal assignment/electrical data
Terminal Use Electrical data
X3/A1-
X3/A1+
Differential voltage input 1
(no jumper between A1R and A1-
Level: -10 V ... +10 V
Resolution: 11 bits + sign
Scaling: When C00034
="0":
±10 V ±2
30
Conversion rate: 1 kHz
Current input
(jumper between A1R and A1-)
Level: -20 mA ... +20 mA
Resolution: 10 bits + sign
Scaling: When C00034
="1":
-20 mA ... -4 mA = -2
30
... 0
+4 mA ... +20 mA = 0 ... 2
30
When C00034 ="2":
±20 mA ±2
30
Conversion rate: 1 kHz
X3/A2-
X3/A2+
Differential voltage input 2 Level: -10 V ... +10 V
Resolution: 11 bits + sign
Scaling: ±10 V ±2
30
Conversion rate: 1 kHz
A1+
A1-
A1-
A1R
A2+
A2-
X3