Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 771
14 Parameter reference
14.2 Parameter list | C00347
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00347
C00348
C00349
Parameter | Name:
C00347 | CAN heartbeat status
Data type: UNSIGNED_8
Index: 24228
d
= 5EA4
h
"CAN on board" system bus: heartbeat protocol
Selection list (read only)
0 Unknown
4 Stopped
5 Operational
127 Pre-operational
Subcodes Info
C00347/1 Status node 1 ... 32
C00347/...
C00347/32
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00348 | CAN status DIP switch
Data type: UNSIGNED_8
Index: 24227
d
= 5EA3
h
• "1" means that the CAN DIP switch has been identified after mains switching and a valid baud rate and node
address have been set.
"0" means that no CAN DIP switch or no valid setting has been identified or the setting has been overwritten by
writing to code C00350
or C00351.
"CAN on board" system bus
Selection list (read only) Info
0 Setting not accepted
1 Setting accepted
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00349 | CAN setting - DIP switch
Data type: UNSIGNED_8
Index: 24226
d
= 5EA2
h
Setting of the CAN DIP switch at the last mains connection
"CAN on board" system bus
Display range (min. value | unit | max. value)
0 255
Subcodes Info
C00349/1 Node address
C00349/2 Baud rate:
0: 500 kbps
1: 250 kbps
2: 125 kbps
3: 50 kbps
4: 1 Mbps
5: 20 kbps
6: 10 kbit/s
14: 800 kbps
255: Automatic recognition
Read access Write access CINH PLC STOP No transfer Scaling factor: 1