14 Parameter reference
14.2 Parameter list | C00577
796
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00577
C00578
C00579
C00580
Parameter | Name:
C00577 | Field weakening controller gain
Data type: UNSIGNED_32
Index: 23998
d
= 5DBE
h
At "0" the P component is deactivated, a pure I-controller is used.
Setting range (min. value | unit | max. value) Lenze setting
0.000 Vs/V 2147483.647 0.000 Vs/V
Read access Write access CINH PLC STOP No transfer Scaling factor: 1000
Parameter | Name:
C00578 | Field weak. contr. reset time
Data type: UNSIGNED_32
Index: 23997
d
= 5DBD
h
At "240000.0 ms" the I component of the field weakening controller is deactivated.
Setting range (min. value | unit | max. value) Lenze setting
1.0 ms 240000.0 2000.0 ms
Read access Write access CINH PLC STOP No transfer Scaling factor: 10
Parameter | Name:
C00579 | Resp. to speed monitoring
Data type: UNSIGNED_32
Index: 23996
d
= 5DBC
h
Response to activation of speed monitoring
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00580 | Resp. to encoder open circuit
Data type: UNSIGNED_32
Index: 23995
d
= 5DBB
h
Response to open circuit in encoder
Danger!
If the encoder is used as motor encoder:
In the event of an error, a safe operation of the motor cannot be ensured anymore!
For safety reasons, the "Fault" response should always be set for this case!
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
13 Quick Stop open loop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1