Lenze 9400 Manual de usuario Pagina 669

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 954
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 668
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 669
13 Diagnostics & fault analysis
13.7 Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CAN on board PDO manager: Faulty configuration [0x00870008]
CAN on board SDO server: Faulty configuration [0x00880000]
CAN on board SDO client: Faulty configuration [0x00890000]
File ProjectSelection.dat defect [0x008c0000]
Module ID (decimal) Error ID (decimal)
135: "CAN on board": CAN-PDO handler 8
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CAN on board: CAN-PDO configuration error
• Faulty project download.
• Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
• Mapping variables have incorrect CANopen indices
according to DS405.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal) Error ID (decimal)
136: "CAN on board": CAN-SDO server 0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CAN on board: A configuration error has occurred in the
CAN SDO server.
• Faulty project download.
• Invalid SDO server settings according to DS301V402
in the Engineer or PLC Designer.
• Repeat download.
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal) Error ID (decimal)
137: "CAN on board": CAN-SDO client 0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CAN on board: A configuration error has occurred in the
CAN SDO client.
• Faulty project download.
Invalid SDO client settings according to DS301V402 in
the Engineer or PLC Designer.
• Repeat download
• Correct CAN settings in the project and regenerate
project.
Module ID (decimal) Error ID (decimal)
140: Application project manager 0
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Reformat memory module (C00002="1030") and repeat
project download.
Vista de pagina 668
1 2 ... 664 665 666 667 668 669 670 671 672 673 674 ... 953 954

Comentarios a estos manuales

Sin comentarios