Lenze 9400 Manual de usuario Pagina 61

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 954
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 60
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 61
4 Drive interface
4.2 Device commands
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.16 Enable controller
The C00002 = "42: Enable controller" device command is used to re-enable an inhibited controller.
Tip!
This device command can also be activated via the icon in the Toolbar.
Related device commands
Inhibit controller
( 60)
Note!
Please note that the controller will only be enabled if all sources for controller inhibit are
reset!
C00158
provides a bit coded representation of all active sources/triggers of a
controller inhibit.
This device command has no status display in C00003
, i.e. the display remains
unchanged showing the previous device command status.
Vista de pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 953 954

Comentarios a estos manuales

Sin comentarios