Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 267
7Braking operation
7.1 Parameter setting
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.1 Parameter setting
Short overview: Parameters for braking operation
7.1.1 Setting the voltage threshold for braking operation
The voltage threshold for braking operation is set via C00173 (mains voltage) and C00181 (reduced
brake chopper threshold). If the brake chopper threshold in the DC bus is exceeded, the brake
transistor is switched on.
Parameter Info Lenze setting
Value Unit
C00129 Brake resistance value 180.0 Ohm
C00130
Rated brake resistor power 5600 W
C00131
Thermal capacity - brake resistor 485 kWs
C00133
Ref.: Brake chopper utilisation Minimum resistance (C00134)
C00134 Min. brake resistance - Ohm
C00137 Brake transistor utilisation - %
C00138 Brake resistor utilisation - %
C00173
Mains voltage 400/415 V
C00181
Reduc. brake chopper threshold 0 V
C00569 Resp. brake trans. ixt > C00570 Warning
C00570
Warning thres. brake transistor 90 %
C00571
Resp. brake res. i2t > C00572 Warning
C00572
Warning thres. brake resistor 90 %
C00573
Resp. to brake transistor overload No response
C00574
Resp. to brake resist. overtemp. No response
C00600
Resp. to DC bus overvoltage Trouble
Greyed out = display parameter
Mains voltage selected in C00173 Effective brake chopper threshold
230 V 390 V - value in C00181
(0 ... 100 V)
400/415 V 725 V - value in C00181
(0 ... 100 V)
460/480 V 765 V - value in C00181 (0 ... 100 V)
500 V 790 V - value in C00181
(0 ... 100 V)