Lenze 9400 Manual de usuario Pagina 182

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 954
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 181
5 Motor interface
5.6 V/f control (VFCplus)
182
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.6.1.1 Defining the V/f characteristic
Linear/square-law characteristic
C00950
serves to select the shape of the characteristic to adjust the characteristic to different load
profiles:
Linear characteristic for drives with constant load torque over the speed.
Square-law characteristic for drives with a linear or square-law load torque over the speed:
Square-law V/f characteristics are mostly used in centrifugal pump and fan drives. However,
it must be checked in each individual case if your pump or fan drive can be used in this
operating mode!
If your pump or fan drive is not suitable for operation with a square-law V/f characteristic,
you have to use the linear or user-definable V/f characteristic or the sensorless vector control
instead of the V/f control.
[5-16] Linear/square-law V/f characteristic
The calculation of the characteristic considers the rated motor voltage (C00090) and the V/f
base frequency (C00951
).
Short overview: Parameters for V/f characteristic
C00090: Rated motor voltage
C00951: V/f base frequency
0
0
C00951
f
soll
0
0
C00951
f
soll

U
C00090
U
C00090

Parameter Info Lenze setting
Value Unit
C00950 VFC: V/f characteristic shape Linear (V/f)
C00951 VFC: V/f base frequency 50 Hz
C00952/1...11
VFC: Frequency interpol. point n Defining a user-defined V/f
characteristic ( 189)
C00953/1...11
VFC: Voltage interpol. point n
C00954/1...11
VFC: Activat. interpol. point n
Vista de pagina 181
1 2 ... 177 178 179 180 181 182 183 184 185 186 187 ... 953 954

Comentarios a estos manuales

Sin comentarios