Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 137
5 Motor interface
5.3 Adjusting motor and controller to each other
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Sequence
The detection of the inverter characteristic is started if
no other identification is active,
no error has occurred, and
no test mode is activated.
If one of the above conditions is not met, the procedure is cancelled and the corresponding
device command status is indicated under C00003
.
If all conditions are met, the motor is energised with a maximum direct current corresponding to
the lower of the following two values:
Ideally, the first value should be reached, the second value is to ensure that the load on the
machine is not too high during this test.
During the procedure, the motor current rises up to the specified maximum value and falls back to
"0" to repeat the cycle with a negative current sign.
The maximum value is reached four times.
The switching frequency is set to rated switching frequency and after the procedure, it is reset
to the original value.
If the switching frequency should be changed later during operation, the characteristic will
be adapted to the current switching frequency.
In the event of a fault
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time
undervoltage), the procedure is terminated with controller inhibit and the detected characteristic is
not considered.
Tip!
From software version V4.0: If it is not possible to determine the so-called "Inverter error
characteristic", or if the results of the determination are incorrect, the device command
C00002
= "70: Load Lenze inverter characteristic" can be used to load a characteristic typical
for the device. Load Lenze INV characteristic
( 69)
or
Rated motor current, see C00088
2 Rated device current
2 1.8 Rated motor current ⋅⋅