Lenze 9400 Manual de usuario Pagina 227

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 954
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 226
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 227
5 Motor interface
5.9 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Failure of multiple motor phases during operation
This function is available from software version V10.0!
The following operating modes enable the detection of multiple motor phases during operation:
VFCplus: V/f control closed loop
SLVC: Sensorless vector control
The monitoring for failure of multiple motor phases is active if
1. C00597
is set to a response other than "No response" (Lenze setting) and
2. the motor voltage exceeds the threshold value parameterised in C02867
.
The "Motor disconnected" fault message is issued if the motor current is lower than the device-
dependent threshold value for > 20 ms.
The monitoring for failure of multiple motor phases can be deactivated if a value of 1000.0 V is
parameterised in C02867
.
Vista de pagina 226
1 2 ... 222 223 224 225 226 227 228 229 230 231 232 ... 953 954

Comentarios a estos manuales

Sin comentarios