Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 69
4 Drive interface
4.2 Device commands
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2.23 Load Lenze INV characteristic
This function extension is available from software version V4.0!
If determination of the so-called "inverter error characteristic" is not possible with the device
command "Calculate inv. characteristic
" or leads to incorrect results, the device command
C00002
= "70: Load Lenze INV characteristic" can be used to load a characteristic which is typical of
the device in question.
• Only possible when the controller is inhibited.
Tip!
Detailed information about the determination of the inverter error characteristic can be
found in the chapter "Motor interface" in the subchapter "Optimising the switching
performance of the inverter". ( 135)
Possible status displays for this device command
Related device commands
Calculate inv. characteristic
( 70)
Status (C00003) Meaning
4621570 Device command in process
4587520 Device command executed successfully
4587521 General fault