14 Parameter reference
14.2 Parameter list | C00120
744
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00120
C00121
C00122
C00123
Parameter | Name:
C00120 | Mot. overload protection (I²xt)
Data type: UNSIGNED_32
Index: 24455
d
= 5F87
h
Threshold for I
2
x t disconnection
• Disconnection is carried out if the thermal motor load (C00066
) is higher than the set threshold.
• A 100 % thermal motor load corresponds to a permanently flowing rated motor current
Note:
When the value is parameterised to 200 %, the monitoring mode of the motor overload protection is switched off!
I2xt motor monitoring
Setting range (min. value | unit | max. value) Lenze setting
0 % 200 105 %
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00121 | Warning threshold motor temperature
Data type: UNSIGNED_32
Index: 24454
d
= 5F86
h
Temperature threshold for motor temperature advance warning
• The response to reaching the threshold can be selected in C00584
.
Motor temperature monitoring
Setting range (min. value | unit | max. value) Lenze setting
0 °C 150 120 °C
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00122 | Heatsink temp. warn. threshold
Data type: UNSIGNED_32
Index: 24453
d
= 5F85
h
Temperature threshold for heatsink temperature advance warning
• The response to reaching the threshold can be selected in C00582
.
Setting range (min. value | unit | max. value) Lenze setting
0°C8585 °C
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00123 | Warning threshold device util.
Data type: UNSIGNED_32
Index: 24452
d
= 5F84
h
Adjustable threshold for I x t advance warning
• The advance warning is sent if the device utilisation (C00064
) is higher than the set threshold.
• The response to reaching the threshold can be selected in C00604
.
Setting range (min. value | unit | max. value) Lenze setting
0 % 100 90 %
Read access Write access CINH PLC STOP No transfer Scaling factor: 1