Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 601
13 Diagnostics & fault analysis
13.3 Drive diagnostics via keypad/bus system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.3 Drive diagnostics via keypad/bus system
Keypad display of the controller status
Display parameters
The parameters listed in the following tables serve to query current states and actual values of the
controller for diagnostic purposes, e.g. by using the keypad, a bus system or the »Engineer« (with an
online connection to the controller).
These parameters are listed in the »Engineer« parameter list and the keypad in the Diagnostics
category.
A detailed description of these parameters can be found in the chapter "Parameter reference
".
( 713)
If the keypad on the front of the controller is connected to the
diagnostic interface X6, the status of the controller is shown
via different icons on the LCD display in the area .
Icon Meaning Note
Controller is ready for operation.
Controller is enabled.
Application in the controller is stopped.
Quick stop active
Controller is inhibited. The power outputs are inhibited.
Controller is ready to switch on.
Speed controller 1 at the limit. The drive is torque-controlled.
Set current limit has been exceeded in motor
or generator mode.
Pulse inhibit active The power outputs are inhibited.
System fault active
Fault active
Trouble active
Quick stop by trouble active
Warning active
Parameter Display
C00183 Device status
C00166 Error description
C00168 Error number
C00051 Actual speed [rpm]
C00052 Motor voltage
C00054 Motor current