Lenze 9400 Manual de usuario Pagina 417

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 954
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 416
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 417
11 Basic drive functions
11.6 Homing
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Note!
For homing, setpoint speeds greater than 30000 rpm are not possible. The speeds
defined for these basic function are internally limited to 30000 rpm.
When the basic function is activated, a start acceleration is considered. Start
acceleration/acceleration reduction when the basic function changes ( 380)
For the encoderless motor control types (from software version V3.0) the following
applies:
The basic function "Homing" can only be activated for V/f control or sensorless vector
control if the position controller has been selected for the position control
(C02570
= "2: position controller active").
The homing modes 14 & 15 are not permissible for the V/f control. If the selection is
impermissible, the error message "Homing mode not allowed" is output.
For the encoderless motor control types (from software version V5.0) the following
applies:
If the V/f control or sensorless vector control is selected, the basic function "Homing" can
be activated, irrespective of the use of the position controller.
If no position controller has been selected for the position control in case of V/f
control or sensorless vector control (C02570
= "1: Phase controller is active"), homing
is only carried out via the speed profile resulting from the homing parameters.
Because of this, the target positions set will only "roughly" be reached.
Vista de pagina 416
1 2 ... 412 413 414 415 416 417 418 419 420 421 422 ... 953 954

Comentarios a estos manuales

Sin comentarios