14 Parameter reference
14.2 Parameter list | C00585
798
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00585
C00586
C00587
Parameter | Name:
C00585 | Resp. to motor overtemp. PTC
Data type: UNSIGNED_32
Index: 23990
d
= 5DB6
h
Response if motor temperature across PTC input T1/T2 too high.
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00586 | Resp. to resolver open circuit
Data type: UNSIGNED_32
Index: 23989
d
= 5DB5
h
Response to open circuit in resolver
Danger!
If the resolver is used as motor encoder:
In the event of an error, a safe operation of the motor cannot be ensured anymore!
For safety reasons, the "Fault" response should always be set for this case!
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
5 Warning
4 Warning locked
3 Quick stop by trouble
13 Quick Stop open loop by trouble
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00587 | Fan control status
Data type: BITFIELD_8
Index: 23988
d
= 5DB4
h
Display area
0x00 0xFF
Value is bit-coded:
Bit 0 Heatsink fan ON
Bit 1 Integral fan ON
Bit 2 Heatsink fan status 1
Bit 3 Heatsink fan status 2
Bit 4 Integral fan status
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access Write access CINH PLC STOP No transfer Scaling factor: 1