Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 607
13 Diagnostics & fault analysis
13.5 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.5 Monitoring
The controller is provided with various monitoring functions which protect the drive against
impermissible operating conditions.
• If a monitoring function responds,
• an entry will be made into the Logbook
of the controller,
• the response (quick stop by trouble, warning, fault, etc.) selected for this monitoring function
is activated,
• the status of the internal device control changes according to the selected response,
controller inhibit is set, and the "DRIVE ERROR" LED on the front of the controller goes on:
See also: Device states ( 97)
LED status displays for the device state ( 599)
Response Logbook entry Display in C00168 Pulse inhibit Controller inhibit Acknowledgeme
nt required
LED
"DRIVE ERROR"
None OFF
Information OFF
Warning
Warning locked
Quick stop by
trouble
Trouble
(after 0.5 s)
Fault
System fault Mains
switching
is required!
Danger!
If automatic restart is enabled (C00142 = "1: Enabled"), the drive can restart
automatically from the "Trouble" and "Safe torque off" device states when the trouble or
request for "Safe torque off active" has been eliminated!
Automatic restart after mains connection/trouble...
( 104)