5 Motor interface
5.4 Servo control (SC)
146
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6. Evaluate the step response:
7. Change the gain Vp under C00075
and the reset time Tn under C00076.
8. Repeat steps 4 ... 6 until the optimum step response of the motor current is reached.
In the optimised state the current rise time typically is 0.5 ... 1 ms.
If the adjustment results are not satisfactory, the decoupling network can be
additionally activated via the setting C00074
= "1". After this, repeat the steps 2 ... 6.
In case of MCS, satisfying results may only be achieved with a current-dependent
correction of the current controller parameters based on the saturation behaviour of the
motor stator leakage inductance. For this purpose, it is required to use a motor with an
electronic nameplate (ENP) or to set the saturation characteristic manually.Correction
of the stator leakage inductance... ( 201)
9. After the optimisation has been completed, deactivate the test mode again (C00398
="0:
Test mode deactivated").
10. Save parameter set (C00002
= "11: Save start parameters").
I
t
I
t
I
t
I
t
I
t
I
t
I
t
I
t
I
t
Vp < Vp opt. Vp = Vp opt. Vp > Vp opt.
Tn < Tn opt.
Tn = Tn opt.
Tn > Tn opt.