Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 291
8 I/O terminals
8.8 Configure exception handling of the outputs
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
See also: Behaviour after task overflow ( 106)
Danger!
In case a task overflow occurs, the brake can be configured to "open". This setting should
be used with caution as the brake is then forcibly opened and does not close even if the
drive controller is inhibited!
Note!
To render the changes effective within the controller, the project has to be updated,
and the changed application has to be transferred to the controller.
During the reset or download of an application, all output signals are set to LOW level
or 0 V for a short time (the state bus, in contrast, is set to HIGH level due to hardware
inversion).