5 Motor interface
5.6 V/f control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.6.2.1 Defining a user-defined V/f characteristic
To individually adjust the motor magnetisation to the real application, a user-definable
characteristic can be selected in C00950
if the linear and square-law characteristic are not suitable.
• The interpolation points (voltage/frequency values) of this characteristic are selected via the 11
subcodes of C00952
and C00953.
• If less interpolation points are required, the interpolation points that are not needed have to be
deactivated via the subcodes of C00954
.
• In the Lenze setting the 11 interpolation points represent a linear characteristic:
[5-18] User-definable characteristic (Lenze setting)
P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11
V 400 V 320 V 240 V 160 V 80 V 0 V 80 V 160 V 240 V 320 V 400 V
f -50 Hz -40 Hz -30 Hz -20 Hz -10 Hz 0 Hz 10 Hz 20 Hz 30 Hz 40 Hz 50 Hz
U [V]
160
0
f [Hz]
240
320
400
10 20 30 40 50
-50 -40 -30 -20 -10
80
C00952/1
C00953/1
C00952/2
C00953/2
C00952/3
C00953/3
C00952/11
C00953/11
P1
P2
P3
P4
P5 P7
P6
P8
P9
P10
P11