11 Basic drive functions
11.3 Quick stop
392
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.3.4 DC-injection braking
This function extension is available from software version V3.0!
Activate DC-injection braking
To activate DC-injection braking through the application, the bActivateDCBrake control input must
be set to TRUE.
A change-over to the "Quick stop active" function state is effected and DC-injection braking with
the braking current set in C00974
is carried out.
Flying restart process after cancelling DC injection braking
If the flying restart mode is activated in C00990
and DC-injection braking is cancelled, a flying
restart process is automatically started to determine the current motor speed if the following
conditions are met:
V/f control or sensorless vector control are selected as motor control in C00006
.
The position control structure is set to "Phase controller is active" in C02570
.
•The MI_bFlyingSyncBlocked control input of the motor interface is not assigned or set to FALSE.
The holding brake, if available, is not applied.
Note!
DC-injection braking is only possible if V/f control or sensorless vector control is selected
as motor control type in C00006
!
Vista de pagina 391