Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 421
11 Basic drive functions
11.6 Homing
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.6.2.1 Behaviour of the home position after mains switching
If the home position/information is also to be available after mains switching, the setting
C02652
= "1: Received" is required.
Another condition for keeping the home position/information after mains switching is the
compliance with the maximum permissible angle of rotation of the encoder.
The maximally permissible angle of rotation can be set in C02653
in angular degree [°] with
regard to the encoder shaft (360° one encoder shaft rotation).
Note!
Due to the internal numerical format and the resolution of one encoder revolution
according to C00100
, the position may not be reconstructed over the complete encoder
range!
The possible number of revolutions can be calculated as follows:
Number of revolutions = 2
(31 - C00100)
Example: For a standard multiturn absolute value encoder with an absolute display
area of 4096 revolutions (±2048), a maximum position resolution of 20 bits per
revolution can be used!
When resolvers or single-turn absolute value encoders are used and the mains is
switched off (24 V supply off), the encoder may only be moved by ½ revolution since
otherwise the home position will get lost due to the ambiguity of the encoder
information.
When multipole resolvers (C00080
> 1) are used, a renewed homing is required after
mains switching due to the ambiguity of the evaluated position.