5 Motor interface
5.9 Monitoring
216
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Structure of the I
2
xt monitoring
The introduction of a two-component model with two time constants (one for the winding and the
other for the housing/laminated core) serves to display the thermal behaviour of the motor up to
500% of the rated current:
[5-34] Structure of the motor monitoring
Calculation with only one time constant
With C01195
= "0 %" the time constant for the winding is not considered and the thermal model is
only calculated with the time constant set for the housing/laminated core.
The setting C01195
= "0 %" is reasonable if for example the two time constants are not known.
The calculation simplified due to this setting corresponds to the calculation in the previous
Lenze devices (e.g. 9300 servo inverter or ECS).
Thermal utilisation of the motor in [%]
k
1
1
(1+p )
t
1
k
2
1
(1+p )
t
2
I
act motor
I
perm motor
(n)
2
Parameter Setting
I
act motor
Actual motor current -
I
perm motor
(n) Permissible motor current (speed-dependent) -
τ
1
Therm. time constant coil C00128/1
k
1
Percentage of the winding in the final temperature C01195
τ
2
Therm. time constant plates C00128/2
k
2
Percentage of the steel plates in the final temperature 100 % - C01195