14 Parameter reference
14.2 Parameter list | C00174
754
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00174
C00175
C00176
C00177
C00178
C00179
Parameter | Name:
C00174 | Undervoltage (LU) threshold
Data type: UNSIGNED_32
Index: 24401
d
= 5F51
h
When C00173 = 4 ... 7, the undervoltage threshold (LU) can be freely selected.
Note:
The minimum adjustable undervoltage threshold depends on the device type:
• Single-axis controller (Single Drive) up to and including BF7: 210 V
Single-axis controller (Single Drive) from BF8s: 400 V
• Multi-axis controller (Multi Drive): 15 V
In the case of an offline parameter setting or when exchanging the memory module between different 9400
HighLine device types, always check the setting of this parameter and adapt it, if required, to prevent a parameter
error after the parameter set download or module change!
Setting range (min. value | unit | max. value) Lenze setting
15 V 400 285 V
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00175 | Service code
Data type: UNSIGNED_32
Index: 24400
d
= 5F50
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00176 | Service code
Data type: UNSIGNED_32
Index: 24399
d
= 5F4F
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00177 | Service code
Data type: UNSIGNED_32
Index: 24398
d
= 5F4E
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00178 | Elapsed-hour meter
Data type: UNSIGNED_32
Index: 24397
d
= 5F4D
h
Display range (min. value | unit | max. value)
0 s 4294967295
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00179 | Power-on time meter
Data type: UNSIGNED_32
Index: 24396
d
= 5F4C
h
Display range (min. value | unit | max. value)
0 s 4294967295
Read access Write access CINH PLC STOP No transfer Scaling factor: 1