Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06 333
9 "CAN on board" system bus
9.9 Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameterise NMT slave (node 2)
1. Accept the settings made in the NMT master in C00386
of the life time factor and the guard
time for the NMTslave:
•Set guard time (C00382
) to 1000 ms.
Set life time factor (C00383
) to 5.
2. Go to C00614
and set the response required in case of a "Life Guarding Event" in the NMT slave.
Tip!
C00625
serves to set which status change is to occur in case of a "Life Guarding Event" in
the NMT slave.
Node guarding telegrams
Remote Transmission Request:
The RTR telegram from the NMT master has the following identifiers:
Identifier (COB-ID) = 1792 + node address of slave = 1792 + 2 = 1794 = 0x702
Remote Transmission Response:
The response telegram from the NMT slave has the same identifier and the "Operational" NMT
status in the user data (s = 5). Telegram structure
( 329)