C00588
C00589
C00591
Parameter | Name:
C00588 | Resp. to failure t. sensor drive
Data type: UNSIGNED_32
Index: 23987
d
= 5DB3
h
Response to error/failure of temperature sensor for heatsink temperature/temperature inside the controller
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00589 | Resp. to CPU temp. > C00126
Data type: UNSIGNED_32
Index: 23986
d
= 5DB2
h
Response if CPU temperature on the control card > variable limit temperature (C00126).
Selection list (Lenze setting printed in bold)
1Fault
5 Warning
0 No response
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C00591 | Resp. to CAN-RPDOx error
Data type: UNSIGNED_8
Index: 23984
d
= 5DB0
h
Response if the corresponding CAN RPDO has not been received in the configured time or with the configured sync.
"CAN on board" system bus
Selection list (Lenze setting printed in bold)
1Fault
2Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
6 Information
0 No response
Subcodes Lenze setting Info
C00591/1 0: No response Response to non-received RPDO1 ... RPDO4
C00591/...