L Firmware 1.37 - 09/2006 587
9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00573
C00573
C00574
C00576
C00577
C00578
Parameter | Name:
C00573 | Resp. to brake chopper overload
Data type: UNSIGNED_32
Index: 24002
d
= 5DC2
h
Response to release of brake chopper monitoring
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT
Parameter | Name:
C00574 | Resp. to overtemp. brake resist.
Data type: UNSIGNED_32
Index: 24001
d
= 5DC1
h
Response to release of brake resistor monitoring
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
2Trouble
3 Quick stop by trouble
4 Warning locked
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT
Parameter | Name:
C00576 | Window speed monitoring
Data type: UNSIGNED_32
Index: 23999
d
= 5DBF
h
Monitoring window for speed control error in [%] of nmax
Setting range
(min. value | unit | max. value) Lenze setting
0 % 100 100 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00577 | Field weakening controller gain
Data type: UNSIGNED_32
Index: 23998
d
= 5DBE
h
With setting "0", the proportional component is deactivated and an integral-action controller is used.
Setting range
(min. value | unit | max. value) Lenze setting
0.000 Vs/V 2147483.647 0.000 Vs/V
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1000
Parameter | Name:
C00578 | Field weak. contr. reset time
Data type: UNSIGNED_32
Index: 23997
d
= 5DBD
h
With setting "240000.0 ms", the integral-action component of the field weakening controller is deactivated.
Setting range
(min. value | unit | max. value) Lenze setting
1.0 ms 240000.0 2000.0 ms
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 10