L Firmware 1.37 - 09/2006 279
9400 HighLine | Parameter setting & configuration
Standard TAs
TA "Actuator – torque" | Quick stop
11.3.8 Quick stop
[11-22] Basic function "Quick stop" (schematic diagram)
r The quick stop function can be activated as follows in the Lenze setting:
– By setting the digital input DI1 to LOW level.
– By a master control via the port LPortAxisIn1:
By setting bit 3 of the bit-coded axis control word.
r Parameter setting: Tab Application parameter Dialog level Overview Quick stop
O Tip!
Detailed information on quick stop can be found in chapter "Basic drive functions"
subchapter "Quick stop
". (C 152)
The basic function "Quick stop" brakes the
drive to standstill within the deceleration
time set for the quick stop function after a
corresponding request independent of the
setpoint selection.
If the quick stop is deactivated, the defined
torque is available again, as the case may
be, an acceleration via the set acceleration
time of the speed limit value is effected.
LS_ManualJog
n
t
è
ç
LS_Brake
n
t
LS_Limiter
n
t
LS_Quickstop
STOP
LS_Torque...
M
Torque
setpoint
n
t
LS_Stop
internal
status machine
DI2
DI6
DI7
DI8
DI1
Status
machine
(basic drive
functions)
Basic drive functions
M
v
F
è
ç
Parameters Lenze setting
Value Unit
C00105 Quick stop deceleration time 0.000 s
C00106
Quick stop S-ramp time 0.00 %
C00107
Reference for deceleration time "Quick stop" Motor reference speed (C00011)
Control inputs of the function Signal configuration
Lenze setting Control input (Multiplexer parameters)
DigIn 1 Activate quick stop 1 C03135/1
Axis control word
bit 03
Activate quick stop 2 C03135/2
FALSE Activate quick stop 3 C03135/3