L Firmware 1.37 - 09/2006 27
9400 HighLine | Parameter setting & configuration
Commissioning
Notes on commissioning using the keypad
3.1 Notes on commissioning using the keypad
For motor with electronic nameplate (ENP)
r A display of the route data offered by ENP via keypad is not provided. The route data
must be edited and optimised individually.
r In order that the motor does not start unintentionally without adjusting the route data,
the maximum current in the Lenze setting is set to "0 A" in C00022
.
r After setting the route data these motor data and the ones read out of the ENP must be
stored with mains failure protection on the memory module of the controller
(C00002
= "11").
For motor without electronic nameplate (ENP)
r The motor and route data must be edited and set individually.
r In order that the motor does not start unintentionally without adjusting the route data,
the maximum current is set to "0 A" in C00022
as factory adjustment.
r After the motor and route data are set, they must be stored with mains failure
protection on the memory module of the controller (C00002
= "11").
Commissioning of the application
r The application must already be stored on the memory module of the controller.
Otherwise, commissioning with keypad only is not possible.
r All application parameters which deviated from the factory adjustment, must be
edited individually. For this purpose, the project planner must provide a corresponding
list (including the motor and route data) for the commissioner.
r In case of a standard set-up the rotor position must be adjusted for synchronous
motors of a third-party manufacturer and Lenze synchronous motors with Stegmann
absolute value encoder.
r After the parameters are set, they must be stored with mains failure protection on the
memory module of the controller (C00002
= "11").