9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
458 Firmware 1.37 - 09/2006 L
Program download is faulty [0x006a0001]
Error during input and output update [0x006a0002]
New application loaded [0x006a0003]
User task 1: Overflow [0x006a0004]
User task 2: Overflow [0x006a0005]
User task 3: Overflow [0x006a0006]
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Transmission of the application to the controller is faulty
(checksum error).
Repeat transmission.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Mains switching. Transmit the application to the
controller again.
Please contact Lenze, if the problem occurs again.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
Application has been changed by transmission from the
engineer or loading from the memory module.
- (Information only)
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Program runtime in user task 1 is too high. Reduce program runtime by means of:
Omitting functions (e.g. by reducing the number of
active FBs).
Optimising the computing time of specific functions
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Program runtime in user task 2 is too high. See remedy for "Overflow of user task 1".
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Program runtime in user task 3 is too high. See remedy for "Overflow of user task 1".