9400 HighLine | Parameter setting & configuration
TAs for interconnection via electrical shaft
TA "Synchronism with mark synchronisation" | "Synchronism" mode"
346 Firmware 1.37 - 09/2006 L
12.3.5.2 Mark synchronisation (master value)
[12-28] "Mark synchronisation" function in signal flow (schematic diagram)
This function serves to carry out a mark synchronisation of the master value via touch
probe sensor.
r Parameter setting: Tab Application parameter Dialog level Overview Synchronism
Master value conditioning
r Configuration: Tab FB editor FB ElectricalShaftVal
n Master value
oMaster value with stretch factor
M
v
Slave
Real master/
Virtual master
C03006 = 0
v
t
Dj
Dj Dj
TP TP
Note!
For this purpose, the touch probe sensor must be connected to the digital input
DI3!
Parameters Lenze setting
Value Unit
C03023 Master value synchronisation (TP) Deactivated
C03612 TP position (register) 0.0000 Unit
C03651 TP limit 1.0000 Unit
C03656 Hysteresis 0.0000 Unit/t