9400 HighLine | Parameter setting & configuration
Motor interface
System block "LS_MotorInterface"
106 Firmware 1.37 - 09/2006 L
MI_bSpeedSetPointLimited
C02569/5 | BOOL
Status signal "Resulting speed setpoint in the limitation"
Signal flow - position follower
(C 184)
Signal flow - speed follower
(C 191)
TRUE The resulting speed setpoint is limited to the limit values
parameterised in C00909/1
and C00909/2.
MI_dnSpeedSetpoint_n
DINT
Current speed setpoint from position control and speed feedforward control or
direct setpoint selection in [%]
After limitation by the upper speed limit value (C00909/1
) and lower speed limit
value (C00909/2
).
100 % Motor reference speed (C00011
)
Signal flow - position follower
(C 184)
Signal flow - speed follower
(C 191)
MI_dnSpeedSetpoint_s
DINT
Current speed setpoint from position control and speed feedforward control or
direct setpoint selection in [rpm]
After limitation by the upper speed limit value (C00909/1
) and lower speed limit
value (C00909/2
).
MI_bSpeedFollowingError
C02569/10 | BOOL
Status signal "Impermissible speed control deviation"
Signal flow - speed follower
(C 191)
TRUE Speed control deviation is higher than the window set in C00576
.
MI_bSpeedCtrlLimited
C02569/6 | BOOL
Status signal "Speed controller in the limitation"
Signal flow - speed follower
(C 191)
Signal flow - position follower
(C 184)
TRUE The speed controller limitation is active.
MI_bTorqueSetpointLimited
C02569/7 | BOOL
Status signal "Total torque setpoint in the limitation"
Signal flow - motor interface
(C 95)
TRUE The total torque setpoint is limited.
MI_dnTorqueSetpoint_n
DINT
Current torque setpoint from speed control and torque feedforward control or direct
setpoint selection
After limitation by MI_dnTorqueLimit_n.
100 % C00057/
2
Signal flow - motor interface (C 95)
MI_-
dnFilteredTorqueSetpoint_n
DINT
Filtered torque setpoint (after jerk limitation and band-stop filter)
100 % C00057/
2
Signal flow - motor interface (C 95)
MI_bCurrentSetpointLimited
C02569/8 | BOOL
Status signal "Setpoint for current controller in the limitation"
Signal flow - motor interface
(C 95)
TRUE The setpoint for the current controller is limited to I
max_device
(C00022).
MI_-
bMotorOverloadWarning
C02569/11 | BOOL
Status signal "Motor overload"
Group signal for warning signals from temperature monitoring (KTY, PTC,
thermal switch) or I
2
xt monitoring.
TRUE One of the monitoring modes for motor overload protection is
active.
MI_-
bSpeedBelowThresholdC19
C02569/9 | BOOL
Status signal "Standstill reached"
TRUE The current speed is below the threshold set in C00019
.
MI_-
dnActualMotorCurrent_n
DINT
Current motor current
100 % I
max_device
(C00789)
Display in C00780
in [A]
Signal flow - motor interface
(C 95)
MI_-
dnActualMotorVoltage_n
DINT
Current motor voltage
100 % 1000 V
Display in C00783
in [V]
Signal flow - motor interface
(C 95)
Output
DIS code | Data type
Value/meaning