9400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00173
560 Firmware 1.37 - 09/2006 L
C00173
C00174
C00175
C00176
Parameter | Name:
C00173 | Mains voltage
Data type: UNSIGNED_8
Index: 24402
d
= 5F52
h
Adaptation of the DC bus voltage thresholds
Check during commissioning and adapt, if necessary.
All drive components in DC bus connections must have the same thresholds.
LU = Undervoltage threshold, OU = Overvoltage threshold
Note:Altering this setting also has an impact on the permissible device utilisation!
In the chapter "Rated data" of the Hardware Manual the corresponding permissible device utilisation for the
different device types at a certain mains voltage and switching frequency is specified.
Selection list
(Lenze setting printed in bold) Information
0 230 V, LU = 150 V Operation on 230 V mains
LU = 150 V, OU = 400 V
Brake chopper threshold = 390 V
1 400/415 V, LU = 285 V Operation on 400 V mains/415 V mains
LU = 285 V, OU = 800 V
Brake chopper threshold = 725 V
2 460/480 V, LU = 328 V Operation on 460 V mains/480 V mains
LU = 328 V, OU = 800 V
Brake chopper threshold = 765 V
3 500 V, LU = 342 V Operation on 500 V mains
LU = 342 V, OU = 800 V
Brake chopper threshold = 790 V
4 230 V, LU configurable Operation on 230 V mains
LU is selected under C00174
OU = 400 V
Brake chopper threshold = 390 V
5 400/415 V, LU configurable Operation on 400 V mains/415 V mains
LU is selected under C00174
OU = 800 V
Brake chopper threshold = 725 V
6 460/480 V, LU configurable Operation on 460 V mains/480 V mains
LU is selected under C00174
OU = 800 V
Brake chopper threshold = 765 V
7 500 V, LU configurable Operation on 500 V mains
LU is selected under C00174
OU = 800 V
Brake chopper threshold = 790 V
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00174 | Threshold - undervoltage (LU)
Data type: UNSIGNED_32
Index: 24401
d
= 5F51
h
With C00173 = 4 ... 7 the LU threshold can be freely selected
Setting range
(min. value | unit | max. value) Lenze setting
15 V 342 285 V
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00175 | Service code
Data type: UNSIGNED_32
Index: 24400
d
= 5F50
h
This code is used internally by the controller and must not be overwritten by the user!
Parameter | Name:
C00176 | Service code
Data type: UNSIGNED_32
Index: 24399
d
= 5F4F
h
This code is used internally by the controller and must not be overwritten by the user!