Vista de pagina 489
9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
490 Firmware 1.37 - 09/2006 L
CAN on board RPDO1: Telegram not received or faulty [0x00870000]
CAN on board RPDO2: Telegram not received or faulty [0x00870001]
CAN on board RPDO3: Telegram not received or faulty [0x00870002]
CAN on board RPDO4: Telegram not received or faulty [0x00870003]
CAN on board PDO manager: Faulty configuration [0x00870008]
Response (Lenze setting printed in bold) Setting: C00591/1 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CAN on board: CAN-IN 1 error
Incorrect PDO telegram length.
Transmission error.
PDO time monitoring has released.
Set the correct telegram length for the CAN master
(transmitter).
Remove electromagnetic interference (e.g. EMC).
Select a different time monitoring or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C00591/2 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CAN on board: CAN-IN 2 error
Incorrect PDO telegram length.
Transmission error.
PDO time monitoring has released.
Set the correct telegram length for the CAN master
(transmitter).
Remove electromagnetic interference (e.g. EMC).
Select a different time monitoring or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C00591/3 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CAN on board: CAN-IN 3 error
Incorrect PDO telegram length.
Transmission error.
PDO time monitoring has released.
Set the correct telegram length for the CAN master
(transmitter).
Remove electromagnetic interference (e.g. EMC).
Select a different time monitoring or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C00591/4 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CAN on board: CAN-IN 4 error
Incorrect PDO telegram length.
Transmission error.
PDO time monitoring has released.
Set the correct telegram length for the CAN master
(transmitter).
Remove electromagnetic interference (e.g. EMC).
Select a different time monitoring or switch off time
monitoring.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
CAN on board: CAN-PDO configuration error
Faulty project download.
Invalid CAN settings according to DS301V402 in the
Engineer or PLC Designer.
Mapping variables have incorrect CANopen indices
according to DS405.
Repeat download.
Correct CAN settings in the project and regenerate
project.