9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
464 Firmware 1.37 - 09/2006 L
DC-bus capacitor: Temperature > CXXXXX [0x00770004]
DC-bus capacitor: overtemperature [0x00770005]
Inside the device: Temperature > CXXXXX [0x00770006]
Inside the device: Overtemperature [0x00770007]
CPU: Temperature > C00126 [0x00770008]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause Remedy
Electrolytic capacitor temperature higher than warning
threshold.
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Electrolytic capacitor temperature higher than limit
temperature (120 °C).
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause Remedy
Inside temperature higher than warning threshold. • Check control cabinet temperature.
• Clean filter.
• Clean controller.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Inside temperature higher than limit temperature (85
°C).
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
Response (Lenze setting printed in bold) Setting: C00589 (; Adjustable response)
: None System fault ; Fault Trouble Quick stop by trouble Warning locked ; Warning Information
Cause Remedy
CPU temperature higher than variable limit temperature
(C00126
).
• Controller ambient temperature too high.
• Dirty fan or ventilation slots.
• Value set under C00126 is too low.
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
• Set a higher value under C00126
.