9400 HighLine | Parameter setting & configuration
Commissioning
Test commissioning
28 Firmware 1.37 - 09/2006 L
3.2 Test commissioning
Worksteps
Initial commissioning of motor/controller:
1. Select motor in the »Engineer« motor catalog
. (C 66)
When the motor connected to the motor has an electronic nameplate (ENP), all motor data are
automatically read out of the ENP and a selection from the motor catalog is not required. Read the
motor data out of the controller (C 66)
2. Accept/adapt route data
. (C 69)
3. Parameterise motor encoder
. (C 70)
Save project and parameter set:
1. Save parameter set
. (C 57)
2. Save »Engineer« project.
Commissioning of the application:
Note:
The following steps require that the technology application "actuator – speed" has been selected in the
»Engineer« application catalog.
See chapter Technology applications (TAs)
:
Commissioning using the »Engineer«
(C 235)
TA "Actuator – speed"
(C 244)
1. Enable controller via terminal RFR.
2. Enable setpoint follower via digital input DI2.
3. Define speed setpoint via analog input 1 (terminal AI1+/AI1-).
4. If required, the direction of rotation can be inverted via the digital input DI3.
5. Check further Basic drive functions
of the applications:
A quick stop can be activated via the digital input DI1. Quick stop
(C 152)
A manual control is available for the setting-up operation. Manual jog
(C 156)
The enable is executed via the digital input DI6.
The digital inputs DI7 and DI8 activate parameterisable setpoints for both directions of rotation.