L Firmware 1.37 - 09/2006 477
9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
Memory module: File system has been formatted [0x007c0000]
Memory module: File system has been restored [0x007c0001]
Analog input 1: Master current < 4 mA [0x007d0000]
Invalid PLC configuration [0x007d0001]
Communication error between device and device module [0x007f0002]
CAN on board: Bus-off [0x00830000]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
File system of the memory module has been formatted. - (Information only)
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
File system of the memory module has been restored. - (Information only)
Response (Lenze setting printed in bold) Setting: C00598 (; Adjustable response)
; None System fault : Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
Master current is in the impermissible range -4 ... +4 mA,
e.g. due to a line break or a defective master current
value encoder.
Only for parameterisation as master current input
(see C00034
).
Remove open circuit.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid control configuration has occurred. Load other application.
Response (Lenze setting printed in bold) Setting: C01501 (; Adjustable response)
: None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked ; Warning Information
Cause Remedy
Communication between controller and extension
module is interrupted, e.g. due to disturbances in the
ambience (EMC), a defective hardware or loose contact.
This monitoring is designed for safe process data
communication.
Remove EMC fault.
Properly connect module.
Switch the mains or restart controller.
Exchange module/controller.
Please contact Lenze, if the problem occurs again.
Response (Lenze setting printed in bold) Setting: C00595 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CAN on board: "Bus-off" state
Too many faulty telegrams received.
Cable defective (e.g. loose contact).
Two nodes with the same ID.
Remove fault (e.g. EMC).
Remove loose contact, screw down adapter.
Assign different node IDs.