9400 HighLine | Parameter setting & configuration
Standard TAs
TA "Actuator – speed" | Speed setpoint conditioning
250 Firmware 1.37 - 09/2006 L
11.2.4 Speed setpoint conditioning
[11-4] Speed setpoint conditioning (schematic diagram)
The speed setpoint is defined in the Lenze setting via the analog input 1 and take place in
both directions (bipolar) and accordingly the driven machine part moves forward or
backward.
r Parameter setting: Tab Application parameter Dialog level Overview
Gain Invert setpointSelection
LS_Speed...
M
Speed
setpoint
DI2DI3DI4
OUT
IN
Ramp generator
%1
%2
%15
Fixed setpoints
Status
machine
(basic drive
functions)
Speed setpoint
AIN1
M
v
Parameters Lenze setting
Value Unit
C03002 Setpoint gain 100.00 %
Setpoint inputs of the function Signal configuration
Lenze setting Setpoint input (Multiplexer parameters)
AIn 1 Speed setpoint C03000