L Firmware 1.37 - 09/2006 535
9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
Acceleration has been limited [0x00b8000c]
Deceleration has been limited [0x00b8000d]
Jerk has been limited [0x00b8000e]
Position target is outside software limit positions [0x00b8000f]
Response (Lenze setting printed in bold) Setting: C02716/3 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
The requested profile acceleration is higher than the
maximum acceleration set in C02705
and has been
limited to this acceleration.
Reduce acceleration of the traversing profile of the
basic function (manual jog, referencing or
positioning).
Increase maximum acceleration (C02705
).
Deactivate monitoring of the limit values by the basic
function "Limiter".
Response (Lenze setting printed in bold) Setting: C02716/3 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
The requested profile deceleration is higher than the
maximum acceleration set in C02705
and has been
limited to this acceleration.
Reduce acceleration of the traversing profile of the
basic function (manual jog, referencing or
positioning).
Increase maximum acceleration (C02705
).
Deactivate monitoring of the limit values by the basic
function "Limiter".
Response (Lenze setting printed in bold) Setting: C02716/3 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
The requested S-ramp time is lower than the minimum
S-ramp time set in C02706
and has been limited to this S-
ramp time.
Increase S-ramp time of the traversing profile of the
basic function (manual jog, referencing or
positioning).
Reduce minimum S-ramp time (C02706
).
Deactivate monitoring of the limit values by the basic
function "Limiter".
Response (Lenze setting printed in bold) Setting: C02716/2 (; Adjustable response)
; None System fault ; Fault ; Trouble : Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
It was tried to position to a target outside the software
limit positions.
Select position target inside the software limit
positions.
Increase permissible traversing range (change setting
of the software limit positions).
Deactivate monitoring of the software limit positions
by the basic function "Limiter".