9400 Technology applications | CiA402 device profile
Parameter setting & configuration
Device control
56 L EDS94TA11010xxxx EN 1.2 - 03/2010
3.7.3.2 Switch on disabled
This is the controller's status after the device has been initialised successfully.
The process data monitoring is active.
Communication is possible.
DC-bus voltage is available.
The controller can be parameterised.
The motor brake, if available, is closed.
The operation is inhibited.
3.7.3.3 Ready to switch on
This is the device status of the controller after the device has been initialised successfully
and after the controller has received the "Shutdown
" command.
The process data monitoring is active.
Communication is possible.
DC-bus voltage is available.
The controller can be parameterised.
The motor brake, if available, is closed.
The operation is inhibited.
Bit pattern for device state "Switch on disabled" in 0x6041 (status word):
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Warning Switch on
disabled
Quick stop Voltage
enabled
Fault Operation
enabled
Switched on Ready to switch
on
X1XX0000
Bit pattern for "Ready to switch on" device state in 0x6041 (status word):
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Warning Switch on
disabled
Quick stop Voltage
enabled
Fault Operation
enabled
Switched on Ready to switch
on
X01X0001
Note!
It is also changed to this device state if in the device states "Switched on" or
"Operation enabled
" the "Shutdown" command is tripped.
The change to the sequential state "Switched on
" is caused by the tripping of the
"Switch on
" command.