9400 Technology applications | CiA402 device profile
Parameter setting & configuration
Parameterisable function blocks
182 L EDS94TA11010xxxx EN 1.2 - 03/2010
3.21 Parameterisable function blocks
This subchapter lists all relevant parameterisable function blocks of the technology
application in alphabetical order with the corresponding parameters.
3.21.1 Adaption_Positioncontroller
3.21.2 Adaption_Speedcontroller
is ans instance of Function
L_TbCurve Adaption of the position controller by characteristic or curve function y = f(x)
Parameter Possible settings Information
C04103 Characteristic mode
0 Entire range
1 Symmetrical to the Y axis Lenze setting
2 Symmetrical to the zero point
C04104/1...9 -200.00 % 200.00 x value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values X1 ... X9.
C04105/1...9 -200.00 % 200.00 y value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values Y1 ... Y9.
is ans instance of Function
L_TbCurve Adaption of the speed controller by the characterstic or curve function y = f(x)
Parameter Possible settings Information
C04100 Characteristic mode
0 Entire range
1 Symmetrical to the Y axis Lenze setting
2 Symmetrical to the zero point
C04101/1...9 -200.00 % 200.00 x value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values X1 ... X9.
C04102/1...9 -200.00 % 200.00 y value of the characteristic function
Subcode 1 ... 9 corresponding to
the support point values Y1 ... Y9.