9400 Technology applications | CiA402 device profile
Parameter setting & configuration
Device control
46 L EDS94TA11010xxxx EN 1.2 - 03/2010
3.7.2 Device control commands
Via the 0x6040
object (control word) "Device Control" commands can be activated to set
the controller to a certain device state:
Tip!
The operating-mode-dependent control bits 4 ... 6 listed in the table are not
important for the tripping of commands but only provide a better readability of the
bit patterns.
Detailed information on the different commands can be obtained from the
following subchapters.
Bit pattern in control word
Device control
command
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reset fault Operating mode-dependent control bits Enable
operation
Quick stop Enable
voltage
Switch on
Shutdown 0 X X XX110
Switch on
0 X X X0111
Enable operation
0 X X X1111
Quick stop
0 X X XX01X
Disable operation
0 X X X0111
Disable voltage
0 X X XXX0X
Reset fault
0 Ê 1 X X XXXXX
X = status is not important