Wiring of the standard device
Basics for wiring according to EMC
Motor cable
5
5.3
5.3.3
5.3−2
EDSVS9332P EN 5.0−07/2013
– it is not interrupted.
ƒ If the motor cable must be opened all the same (e.g. due to chokes,
contactors, or terminals):
– The unshielded cable ends may not be longer than 100 mm
(depending on the cable cross−section).
– Install chokes, contactors, terminals etc. spatially separated from
other components (with a min. distance of 100 mm).
– Install the shield of the motor cable directly before and behind the
point of separation to the mounting plate with a large surface.
ƒ Connect the shield with a large surface to PE in the terminal box of the
motor at the motor housing.
– Metal EMC cable glands at the motor terminal box ensure a large
surface connection of the shield with the motor housing.
Motor supply cable Cable gland
Motor supply cable
max. 500mm
Large-surface
contactof
cable shield
Braid
Heat-shrinkable tube
Cablegland acc.toEMC with
high degree ofprotection
Cable gland
8200EMV023 8200EMV024
Fig. 5.3−1 Shielding of the motor cable