Wiring of the standard device
Standard devices in the power range 55 ... 75 kW
Motor connection
5
5.7
5.7.6
5.7−7
EDSVS9332P EN 5.0−07/2013
5.7.6 Motor connection
Note!
ƒ Fusing the motor cable is not required.
ƒ The drive controller features 2 connections for motor
temperature monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal
contact (NC contact).
– Pins X8/5 and X8/8 of the incremental encoder input (X8) for
connecting a KTY thermal sensor.
Wire T1, T2 only if the motor is equipped with a PTC thermistor or thermal
contact (NC contact).
ƒ An "open" cable acts like an antenna and can cause faults on the drive
controller.
Danger!
ƒ All control terminals only have basic insulation (single
isolating distance) after connecting a PTC thermistor or a
thermal contact.
ƒ Protection against accidental contact in case of a defective
isolating distance is only guaranteed through external
measures, e.g. double insulation.
PE
U
VW
T1 T2
+UG -UG
PES
PES
PE
M
3~
J>
PES
PES
PES
2.7 k
MONIT-OH8
15 V
3.3 k
7.4 k
9300vec139
Fig. 5.7−3 Circuit diagram of motor connection with PTC thermistor or thermal contact (NC
contact) at T1, T2
Motor with PTC thermistor or
thermal contact (NC contact)