Lenze EVS9332xP Manual de usuario Pagina 107

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 445
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 106
Wiring of the standard device
Standard devices in the power range 15 ... 30 kW
Important notes
5
5.5
5.5.2
5.5−3
EDSVS9332P EN 5.0−07/2013
5.5.2 Important notes
To gain access to the power connections, remove the cover:
Remove the cover of the drive controller
0
1
1. Remove the screws
2. Lift cover up and detach it
9300vec113
Installation material required from the scope of supply:
Description Use Quantity
Hexagon nut M6 (DIN 934) Connection of supply cables (mains, +U
G
, −U
G
)
and motor cable to the stud bolts
10
Washer Æ 6 mm (DIN 125) For hexagon nut M6 10
Spring washer Æ 6 mm (DIN 127) For hexagon nut M6 10
Grommet Motor cable 1
Shield connection support Support of the shield sheet for motor cable 1
Self−tapping screw Æ 4 × 14 mm Fastening of shield connection support 2
Shield sheet Shield connection for motor cable 1
5.5.3 Mains connection, DC supply
Note!
ƒ If a mains filter or RFI filter is used and the cable length
between mains/RFI filter and drive controller exceeds
300 mm, install a shielded cable.
ƒ For DC−bus operation or DC supply, we recommend using
shielded DC cables.
Vista de pagina 106
1 2 ... 102 103 104 105 106 107 108 109 110 111 112 ... 444 445

Comentarios a estos manuales

Sin comentarios