Wiring of the standard device
Standard devices with a power of 45 kW
Mains connection, DC supply
5
5.6
5.6.3
5.6−4
EDSVS9332P EN 5.0−07/2013
5.6.3 Mains connection, DC supply
Note!
ƒ If a mains filter or RFI filter is used and the cable length
between mains/RFI filter and drive controller exceeds
300 mm, install a shielded cable.
ƒ For DC−bus operation or DC supply, we recommend using
shielded DC cables.
PE
+UG -UG
L1 L2
L3
3
01 2
L1, L2, L3
+U , -U
PE
GG
M8
15 Nm
132 lb-in
}
+
PE
9300vec126
Fig. 5.6−2 Mains connection, DC supply for 45 kW controller
PE stud
Connect PE cable with ring cable lug
Conductive surface
Shield clamp
Place shield with large surface on control cabinet mounting plate and fasten
with shield clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also place the shield on the PE stud
Mains and DC bus connection
L1, L2, L3: Connection of mains cable with ring cable lugs
+U
G
, −U
G
: Connection of DC−bus components or connection of the controller
in the DC−bus system (see system manual)