Wiring of the standard device
Standard devices in the power range 15 ... 30 kW
Mains choke/mains filter assignment
5
5.5
5.5.5
5.5−6
EDSVS9332P EN 5.0−07/2013
Supply conditions
Range Description
Fuses l Only according to UL 248
l Mains short−circuit current up to 5000 A
rms
: All classes permissible
l Mains short−circuit current up to 50000 A
rms
: Only classes "J", "T" or "R"
permissible
Cables l Only in accordance with UL
l The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300 Rated fuse current Cable cross−section
Fuse L1, L2, L3, PE
Type [A] [AWG]
Operation with mains choke/mains filter
EVS9327−xP
35 8
EVS9328−xP 60 4
EVS9329−xP 80 4
5.5.5 Mains choke/mains filter assignment
9300 Mains choke Interference voltage category according to EN 61800−3 and motor cable length
Component Component
Type C2 max. [m] C1 max. [m]
EVS9327−xP ELN3−0088H035−001 EZN3A0110H030 25
E82ZN22334B230 10
E82ZZ15334B230
1)
10
E82ZN22334B230 50
EZN3B0110H030U
2)
50
E82ZZ15334B230
1)
50
EVS9328−xP ELN3−0075H045
EZN3A0080H042 25 E82ZN22334B230 10
E82ZN22334B230 50 EZN3B0080H042 50
EVS9329−xP ELN3−0055H055
EZN3A0055H060 25 E82ZN30334B230 10
E82ZN30334B230 50 EZN3B0055H060 50
1)
RFI filter
2)
Footprint filter
Installation to UL